HEAT PUMPS ARE MONEY LOSERS IN MY VERMONT HOUSE, AS THEY ARE IN ALMOST ALL NEW ENGLAND HOUSES
https://www.windtaskforce.org/profiles/blogs/heat-pumps-are-money-l...
Vermont “Electrify-Everything” Goals Will Cost $Billions and Will Reduce Little CO2
The Vermont state government wants to electrify-everything (heat pumps, electric cars, and transit and school buses, no matter the: 1) Very high turnkey capital cost; 2) Very meager energy cost savings; 3) Very meager CO2 reductions, on an A-to-Z, lifetime basis.
VT-DPS CADMUS Survey of Vermont Heat Pumps
VT-DPS commissioned CADMUS to perform a survey of Vermont air source heat pumps (HPs), after numerous complaints from HP users regarding: 1) high electric bills and 2) minimal annual savings after installing HPs
The report and VT-DPS found the average energy cost savings regarding HPs was about $200/HP, as proven by the CADMUS survey report of operating data of 77 HPs at 65 sites. See URL
https://publicservice.vermont.gov/sites/dps/files/documents/2017%20...
Those meager energy savings would be more than offset by the annual amortizing cost of $4,500/HP at 6%/y for 15 years, plus any annual maintenance costs, and parts and labor costs. HPs are significant money losers for Vermonters. See URLs
The main result of Vermont’s HP saga has been:
1) Lucrative benefits to the Efficiency-Vermont-approved HP installers
2) Lucrative benefits to Canadian-owned GMP, which sells a lot more high-priced electricity, using the same poles and wires.
3) Everyone else getting royally screwed; an example of “fighting” climate change; Don-Quixote tilting at wind mills.
Weatherizing Vermont’s Energy-Hog Houses
Please stop using the word “weatherizing”, which usually costs about $10,000/house.
Such a measure is not anywhere near sufficient for HPs to displace 100% of fossil fuel Btus with electricity Btus; it is a mere band-aid;
akin to whistling past the graveyard.
For 100% displacement, 2 to 3 HPs, with multiple heads, are required, PLUS a wood/propane/fuel oil stove on colder days.
A house would have to be highly sealed, highly insulated, R40 walls, R60 ceiling, R20 basement, R7 windows, R10 doors, with exhaust heat recovery system, etc., to have HPs economically displace 100% of fossil fuel Btus with electricity Btus.
Such houses do exist in Vermont, but are less than 2 to 3% of the entire housing stock.
Vermont has a government-subsidized weatherizing program, that aims to decrease the energy consumption for heating, cooling and electricity of average Vermont houses. The average weatherizing cost is about $10,000/house.
However, owners who have weatherized should not think their house has become suitable for HPs to displace 100% of fossil fuel Btus with electricity Btus. Nothing could further from the truth!
I have a well-sealed, well-insulated house, oriented/designed for passive solar gain, i.e., it is already weatherized, but my 3 HPs, with 6 heads, economically displace only 35% of my fossil fuel Btus with electricity Btus, based on 3 years of measured operating data.
One HP with one head, in an average Vermont house, displaces only 27.6% of the fossil fuel Btus with electricity Btus, as confirmed by the CADMUS survey report.
All of the above is well known by energy engineers at VT-DPS, and EAN, and VEIC, and Efficiency-Vermont, etc.
Those engineers likely know of some very energy-efficient Vermont houses, with HPs that displace 100% of fossil fuel Btus with electricity Btus, year-after-year.
HPs are Uneconomical at Low Temperatures
HPs are very uneconomical at low temperatures, which is exactly the condition when your house requires the most space heat. With HP system losses, aka overhead of about 10%, it would be almost like heating your house with electric heat; a very expensive hardship on cold days.
If a house had a space heat requirement of 11,500 Btu/h at 47F, the propane cost would be about 40 c/h, but the HP electricity cost would be about 16 c/h, for a saving of about 24 c/h
If a house had a space heat requirement of 35,000 Btu/h at 0F, the propane cost would be about 121 c/h, but the HP electricity cost would be about 141 c/h, for a loss of about 20 c/h
My Experience with HPs in my Well-Insulated, Well-Sealed House
I installed three heat pumps by Mitsubishi, rated 24,000 Btu/h at 47F, Model MXZ-2C24NAHZ2, each with 2 heads, each with remote control; 2 in the living room, 1 in the kitchen, and 1 in each of 3 bedrooms.
The HPs have DC variable-speed, motor-driven compressors and fans, which improves the efficiency of low-temperature operation.
The HPs last about 15 years.
Turnkey capital cost was $24,000, less $2,400 subsidy from GMP
http://www.windtaskforce.org/profiles/blogs/vermont-co2-reduction-o...
My Well-Sealed, Well-Insulated House
The HPs are used for heating and cooling my 35-y-old, 3,600 sq ft, well-sealed/well-insulated house.
The basement, 1,200 sq ft, has a near-steady temperature throughout the year, because it has 2” of blueboard, R-10, on the outside of the concrete foundation and under the basement slab, which has saved me many thousands of space heating dollars over the 35 years.
I do not operate my HPs below 10F to 15F (depending on sun and wind conditions), because all HPs would become increasingly less efficient with decreasing outdoor temperatures.
The HP operating cost per hour would become greater than of my efficient propane furnace. See table 3
High Electricity Prices
Vermont forcing, with subsidies and/or GWSA mandates, the build-outs of expensive RE electricity systems, such as wind, solar, batteries, etc., would be counter-productive, because it would:
1) Increase already-high electric rates and
2) Worsen the already-poor economics of HPs (and of EVs)!!
https://www.windtaskforce.org/profiles/blogs/high-costs-of-wind-sol...
My Energy Cost Reduction is Minimal
- HP electricity consumption was from my electric bills, and an HP system electric meter.
- Vermont electricity prices, including taxes, fees and surcharges, are assumed at 20 c/kWh.
- My HPs provide space heat to 2,300 sq ft, about the same area as an average Vermont house
- Two small propane heaters (electricity not required) provide space heat to my 1,300 sq ft basement
- I operate my HPs at temperatures of 10 to 15F and greater (depending on wind and sun conditions)
- I operate my traditional propane system at temperatures of 10f to 15F and less
- My average HP coefficient of performance, COP, was 2.64
- My HPs required 2,489 kWh to replace 35% of my fossil Btus.
- My HPs would require 8,997 kWh, to replace 100% of my fossil Btus.
https://afdc.energy.gov/files/u/publication/fuel_comparison_chart.pdf
https://www.nature.com/articles/s41597-019-0199-y
https://acrpc.org/wp-content/uploads/2021/04/HeatPumps-ACRPC-5_20.pdf
Before HPs: I used 100 gal for domestic hot water + 250 gal for 2 stoves in basement + 850 gal for Viessmann furnace, for a total propane of 1,200 gal/y
After HPs: I used 100 gal for DHW + 250 gal for 2 stoves in basement + 550 gal for Viessmann furnace + 2,489 kWh of electricity.
My propane cost reduction for space heating was 850 - 550 = 300 gallon/y, at a cost of $2.339/gal (buyers plan) = $702/y
My displaced fossil Btus was 100 x (1 - 550/850) = 35%, which is better than the Vermont average of 27.6%
My purchased electricity cost increase was 2,489 kWh x 20 c/kWh = $498/y
My energy cost savings due to the HPs were 702 - 498 = $204/y, on an investment of $24,000!!
Amortizing Heat Pumps
Amortizing the 24000 – 2400 = $21,600 turnkey capital cost at 6%/y for 15 years costs about $2,187/y.
This is in addition to the amortizing of my existing propane system. I am losing money.
https://www.myamortizationchart.com
Other Annual Costs
There likely would be annual cleaning of HPs at $200/HP, and parts and labor, as the years go by.
This is in addition to the annual service calls and parts for my existing propane system. I am losing more money.
My Energy Savings of Propane versus HPs
Site Energy Basis: RE folks claim there would be a major energy reduction, due to using HPs. They compare the thermal Btus of 300 gallon of propane x 84,250 Btu/gal = 25,275,000 Btu vs the electrical Btus of 2,489 kWh of electricity x 3,412 Btu/kWh = 8,492,469 Btu. However, that comparison would equate thermal Btus with electrical Btus, which all ethical engineers know is an absolute no-no.
A-to-Z Energy Basis: A proper comparison would be thermal Btus of propane vs thermal Btus fed to power plants, i.e., 25,275,000 Btu vs 23,312,490 Btu, i.e., a minor energy reduction. See table 1A
BTW, almost all RE folks who claim a major energy reduction from HPs, do not know how to compose below table, and yet these ignorami mandate others what to do to save the world.
Table 1A, Energy Savings
|
|
|
Heat in propane, Btu/y, HHV
|
25275000
|
|
Fuel to power plant, Btu/y
|
|
23312490
|
Fuel to power plant, kWh/y
|
|
6833
|
Conversion efficiency
|
|
0.4
|
Fed to grid, kWh
|
|
2733
|
Transmission loss adjustment, 2.4%
|
|
2667
|
Distribution loss adjustment, 6.7%
|
|
2489
|
Heat in propane, Btu/gal, HHV
|
84250
|
|
Purchased propane, gal/y
|
300
|
|
Purchased electricity, kWh/y
|
|
2489
|
Heat in propane Btu/gal, LHV
|
84250
|
|
Standby, kWh
|
|
91
|
Defrost, kWh
|
|
154
|
To compressor, kWh
|
|
2244
|
COP
|
|
2.64
|
Heat for space heat, kWh
|
|
5926
|
Btu/kWh
|
|
3412
|
Furnace efficiency
|
0.8
|
|
Btu/y for space heat
|
20220000
|
20220000
|
.
Comparison of CO2 Reduction in my House versus EAN Estimate
My CO2 emissions for space heating, before HPs, were 850 gal/y x 12.7 lb CO2/gal, from combustion = 4.897 Mt/y
My CO2 emissions for space heating, after HPs, were calculated in two ways:
1) Market based, based on commercial contracts, aka power purchase agreements, PPAs
2) Location based, based on fuels combusted by power plants connected to the NE grid
See Appendix for details.
Market Based
Per state mandates, utilities have PPAs with Owners of low-CO2 power sources, such as wind, solar, nuclear, hydro, and biomass, in-state and out-of-state.
Utilities crow about being “low-CO2”, or “zero-CO2” by signing PPA papers, i.e., without spending a dime.
Energy Action Network, a pro-RE-umbrella organization, uses 33.9 g CO2/kWh (calculated by VT-DPS), based on utilities having PPAs with low-CO2 power sources.
Using that low CO2 value makes HPs look extra good compared with fossil fuels.
My CO2 of propane was 550 gal/y x 12.7 lb CO2/gal, combustion only = 3.168 Mt/y
My CO2 of electricity was 2,489 kWh x 33.9 g/kWh = 0.084 Mt/y
Total CO2 = 3.168 + 0.084 = 3.253 Mt/y
CO2 reduction is 4.897 - 3.253 = 1.644 Mt/y, based on the 2018 VT-DPS “paper-based” value of 33.9 g CO2/kWh
Location Based
Utilities physically draw almost all of their electricity supply from the high-voltage grid
If utilities did not have PPAs, and would draw electricity from the high-voltage grid, they would be stealing.
ISO-NE administers a settlement system, to ensure utilities pay owners per PPA contract.
Electricity travels as electric-magnetic waves, at near the speed of light, i.e., from northern Maine to southern Florida, about 1,800 miles in 0.01 second.
There is no physical basis for lay RE folks to talk about there being a “VT CO2” or a “NH CO2”, etc.
All electricity on the NE grid has one value for g CO2/kWh.
ISO-NE, the NE grid operator, calculated that value at 317 g CO2/kWh, at wall outlet, for 2018
My CO2 of propane was 550 gal/y x 12.7 lb CO2/gal, combustion only = 3.168 Mt/y
My CO2 of electricity was 2,489 kWh x 317 g/kWh = 0.789 Mt/y
Total CO2 = 3.168 + 0.789 = 3.937 Mt/y
CO2 reduction is 4.897 - 3.937 = 0.939 Mt/y, based on the 2018 “real world” value of 317 g CO2/kWh, as calculated by ISO-NE
Cost of CO2 Reduction is ($2059/y, amortizing - $204/y, energy cost savings + $200/y, service, parts, labor) / (0.939 Mt/y, CO2 reduction) = $2,188/Mt, which is outrageously expensive.
https://www.eia.gov/environment/emissions/co2_vol_mass.php
https://afdc.energy.gov/files/u/publication/fuel_comparison_chart.pdf
EAN Excessive CO2 Reduction Claim to Hype HPs
EAN claims 90,000 HPs, by 2025, would reduce 0.37 million metric ton of CO2, in 2025, or 0.37 million/90,000 = 4.111 Mt/y.
https://www.eanvt.org/wp-content/uploads/2020/03/EAN-report-2020-fi...
EAN achieves such a high value, because EAN assumes 100% displacement of fuel (gas, propane, fuel oil), which is completely unrealistic, because the actual fuel displacement in Vermont houses with HPs was only 27.6%, based on a VT-DPS-sponsored survey of HPs in Vermont, and 35% in my well-insulated/well-sealed VT house, as above stated.
The EAN 100% claim would be true, only for highly sealed and highly insulated houses, which represent about 2% of all Vermont houses.
In addition, the average Vermont house would need 2 to 3 HPs, with 4 to 6 heads, at a turnkey cost of at least $20,000, to achieve 100% displacement. See URL
Table 1/CO2 Reduction
|
With HP
|
With HP
|
Fuel displaced 35%
|
Electricity
|
Electricity
|
|
Market based
|
Location based
|
Electricity CO2, g/kWh
|
33.9
|
317
|
CO2 of 2489 kWh, Mt/y
|
0.084
|
0.789
|
CO2 of 550 gal of propane, Mt/y
|
3.168
|
3.168
|
Total CO2 with HPs, Mt/y
|
3.253
|
3.957
|
CO2 of 850 gal of propane, Mt/y
|
4.897
|
4.897
|
CO2 reduction by my HPs, Mt/y
|
1.644
|
0.939
|
.
|
|
|
Fuel displaced 100%
|
|
|
CO2 reduction by EAN, Mt/y
|
4.111
|
|
Coddling RE Businesses to Help Them be Profitable
Heavily subsidized businesses selling/installing/servicing HPs, etc., will be collecting hundreds of $millions each year over the decades, while already-struggling, over-regulated, over-taxed Vermonters will be further screwed out of a decent standard of living.
HP boosters Sens. Bray, McDonald, etc., know about those dreadful HP results in Vermont, and yet they continue shilling for HPs.
All these expensive Vermont GWSA efforts will be having ZERO IMPACT ON GLOBAL WARMING.
Burning Wood or Wood Pellets
If you have a wood stove or pellet stove, by all means use it, because it is the lowest-cost way to space heat houses, including Vermont energy-hog houses.
Be aware, the exhaust of woodstoves has mostly submicron particles (less than one millionth of a meter), that are most harmful to health, especially to: 1) people with heart and lung diseases, and 2) infants and children
A wood-burning open fireplace has negative efficiency, i.e., is sucks more heat out of a space, than it adds heat to a space. Do not use it at temperatures less than 35F.
These URLs are provided for information:
https://www.windtaskforce.org/profiles/blogs/electric-bus-systems-l...
https://www.windtaskforce.org/profiles/blogs/poor-economics-of-elec...
http://www.windtaskforce.org/profiles/blogs/electric-vehicles-compa...
http://www.windtaskforce.org/profiles/blogs/vermont-co2-reduction-o...
http://www.windtaskforce.org/profiles/blogs/vermont-co2-reduction-o...
http://www.windtaskforce.org/profiles/blogs/the-proper-basis-for-ca...
High Electricity Prices
Vermont forcing, with subsidies and/or GWSA mandates, the build-outs of expensive RE electricity systems, such as wind, solar, batteries, etc., would be counter-productive, because it would:
1) Increase already-high electric rates and
2) Worsen the already-poor economics of HPs (and of electric cars and buses)
https://www.windtaskforce.org/profiles/blogs/high-costs-of-wind-sol...
PART 1
Any experienced energy systems engineer can readily calculate the hourly cost of operating HPs and propane furnaces.
The HP operating cost per hour would become greater than of an efficient propane furnace, because HPs would become increasingly less efficient with decreasing temperatures. See table 3
Energy Cost Reduction Due to HPs is Minimal
- HP electricity consumption was from my electric bills
- Vermont electricity prices, including taxes, fees and surcharges, are about 20 c/kWh.
- My HPs provide space heat to 2,300 sq ft, about the same area as an average Vermont house
- Two small propane heaters provide space heat to my 1,300 sq ft basement
- I operate my HPs at temperatures of 15F, or greater; less $/h than propane
- I operate my wall-hung propane heater at temperatures of 15F, or less; less $/h than HP
- My average HP coefficient of performance, COP, was 2.64; if I operated my HPs at less than 10F, the average COP would become 2.0 or less
- My HPs required 2,489 kWh to displace 35% of my fuel.
- My HPs would require 8,997 kWh, to replace 100% of my fuel.
- The average Vermont house COP is about 3.34, because the HPs typically operate at about 28F to 35F and above
- The average Vermont house requires 2,085 kWh to displace 27.6% of its fuel, per VT-DPS/CADMUS survey. See URLs
https://afdc.energy.gov/files/u/publication/fuel_comparison_chart.pdf
https://www.nature.com/articles/s41597-019-0199-y
https://acrpc.org/wp-content/uploads/2021/04/HeatPumps-ACRPC-5_20.pdf
Before HPs: I used 100 gal for domestic hot water + 250 gal for 2 stoves in basement + 850 gal for Viessmann furnace, for a total propane of 1,200 gal/y
After HPs: I used 100 gal for DHW + 250 gal for 2 stoves in basement + 550 gal for Viessmann furnace + 2,489 kWh of electricity.
My propane cost reduction for space heating was 850 - 550 = 300 gallon/y, at a cost of 2.339/gal = $702/y
My displaced fuel was 100 x (1 - 550/850) = 35%, which is better than the Vermont average of 27.6%
My purchased electricity cost increase was 2,489 kWh x 20 c/kWh = $498/y
My energy cost savings due to the HPs were 702 - 498 = $204/y, on an investment of $24,000!!
Amortizing Heat Pumps
Amortizing the $24,000 turnkey capital cost at 3.5%/y for 15 years costs about $2,059/y.
This is in addition to the amortizing of my existing propane system. I am losing money.
https://www.myamortizationchart.com
Other Annual Costs
There likely would be service calls and parts for the HP system, as the years go by.
This is in addition to the annual service calls and parts for my existing propane system. I am losing more money.
Table 1
|
Vermont HPs
|
My HPs
|
My HPs, if 100%
|
Before HPs
|
|
Per CADMUS survey
|
|
|
Propane
|
Fuel Displacement, %
|
27.6
|
35%
|
100%
|
100%
|
Operation
|
Down to 28F
|
Down to 15F
|
Down to -10F
|
|
Purchased electricity, kWh
|
2085
|
2489
|
8997
|
|
Standby, kWh
|
76
|
91
|
329
|
|
Defrost, kWh
|
129
|
154
|
557
|
|
Electricity to HPs, kWh
|
1880
|
2244
|
8111
|
|
COP, excl HP self-use
|
3.34
|
2.64
|
2.07
|
|
Space heat, kWh
|
6272
|
5926
|
16791
|
|
Btu/kWh
|
3412
|
3412
|
3412
|
|
Space heat, Btu/site
|
21400000
|
20220010
|
57290000
|
57290000
|
Efficiency
|
|
|
|
0.8
|
Btu/gal, LHV
|
|
|
|
84250
|
Unit cost
|
0.20
|
0.20
|
0.20
|
2.3390
|
Electricity cost, $
|
417
|
498
|
1799
|
|
Propane, gal
|
|
550
|
0
|
850
|
Propane cost, $
|
|
1286
|
0
|
|
Total energy cost, $
|
|
1784
|
1799
|
1988
|
Energy savings, $
|
|
204
|
189
|
|
Energy Savings of Propane versus HPs
Site Energy Basis: RE folks claim there would be a major energy reduction, due to using HPs. They compare the thermal Btus of 300 gallon of propane x 84,250 Btu/gal = 25,275,000 Btu vs the electrical Btus of 2,489 kWh of electricity x 3,412 Btu/kWh = 8,492,469 Btu.
However, that comparison would equate thermal Btus with electrical Btus, which all engineers know is an absolute no-no.
A-to-Z Energy Basis: A proper comparison would be thermal Btus of propane vs thermal Btus fed to power plants, i.e., 25,275,000 Btu vs 23,312,490 Btu, i.e., a minor energy reduction. See table 1A
NOTE:
Almost all RE folks involved with the GWSA claim energy reductions from HPs.
They likely do not know how to compose table 1A
However, they mandate Vermonters what to do, to save the world from Climate Change
This is a case of the blind leading the gullible
Table 1A, Energy Savings
|
|
|
Heat in propane, Btu/y, HHV
|
25275000
|
|
Fuel to power plant, Btu/y
|
|
23312490
|
Fuel to power plant, kWh/y
|
|
6833
|
Conversion efficiency
|
|
0.4
|
Fed to grid, kWh
|
|
2733
|
Transmission loss adjustment, 2.4%
|
|
2667
|
Distribution loss adjustment, 6.7%
|
|
2489
|
Heat in propane, Btu/gal, HHV
|
84250
|
|
Purchased propane, gal/y
|
300
|
|
Purchased electricity, kWh/y
|
|
2489
|
Heat in propane Btu/gal, LHV
|
84250
|
|
Standby, kWh
|
|
91
|
Defrost, kWh
|
|
154
|
To compressor, kWh
|
|
2244
|
COP
|
|
2.64
|
Heat for space heat, kWh
|
|
5926
|
Btu/kWh
|
|
3412
|
Furnace efficiency
|
0.8
|
|
Btu/y for space heat
|
20220000
|
20220000
|
PART 2
CO2 Reduction due to HPs is minimal
My CO2 emissions for space heating, before HPs, were 850 gal/y x 12.7 lb CO2/gal, from combustion = 4.897 Mt/y
My CO2 emissions for space heating, after HPs, were calculated in two ways:
1) Market based, based on commercial contracts, aka power purchase agreements, PPAs
2) Location based, based on fuels combusted by power plants connected to the NE grid
See Appendix for details.
Market Based
Per state mandates, utilities have PPAs with Owners of low-CO2 power sources, such as wind, solar, nuclear, hydro, and biomass, in-state and out-of-state.
Utilities crow about being “low-CO2”, or “zero-CO2” by signing PPA papers, i.e., without spending a dime.
Energy Action Network, a pro-RE-umbrella organization, uses 33.9 g CO2/kWh (calculated by VT-DPS), based on utilities having PPAs with low-CO2 power sources.
Using that low CO2 value makes HPs look extra good compared with fossil fuels.
My CO2 of propane was 550 gal/y x 12.7 lb CO2/gal, combustion only = 3.168 Mt/y
My CO2 of electricity was 2,489 kWh x 33.9 g/kWh = 0.084 Mt/y
Total CO2 = 3.168 + 0.084 = 3.253 Mt/y
CO2 reduction is 4.897 - 3.253 = 1.644 Mt/y, based on the 2018 VT-DPS “paper-based” value of 33.9 g CO2/kWh
Location Based
Utilities physically draw almost all of their electricity supply from the high-voltage grid
If utilities did not have PPAs, and would draw electricity from the high-voltage grid, they would be stealing.
ISO-NE administers a settlement system, to ensure utilities pay owners per PPA contract.
Electricity travels as electric-magnetic waves, at near the speed of light, i.e., from northern Maine to southern Florida, about 1,800 miles in 0.01 second.
There is no physical basis for lay RE folks to talk about there being a “VT CO2” or a “NH CO2”, etc.
All electricity on the NE grid has one value for g CO2/kWh.
ISO-NE, the NE grid operator, calculated that value at 317 g CO2/kWh, at wall outlet, for 2018
My CO2 of propane was 550 gal/y x 12.7 lb CO2/gal, combustion only = 3.168 Mt/y
My CO2 of electricity was 2,489 kWh x 317 g/kWh = 0.789 Mt/y
Total CO2 = 3.168 + 0.789 = 3.897 Mt/y
CO2 reduction is 4.897 - 3.897 = 0.939 Mt/y, based on the 2018 “real world” value of 317 g CO2/kWh, as calculated by ISO-NE
Cost of CO2 Reduction is ($2059/y, amortizing - $204/y, energy cost savings + $200/y, service, parts, labor) / (0.939 Mt/y, CO2 reduction) = $2,188/Mt, which is outrageously expensive.
https://www.eia.gov/environment/emissions/co2_vol_mass.php
https://afdc.energy.gov/files/u/publication/fuel_comparison_chart.pdf
EAN Excessive CO2 Reduction Claim to Hype HPs
EAN claims 90,000 HPs, by 2025, would reduce 0.37 million metric ton of CO2, in 2025, or 0.37 million/90,000 = 4.111 Mt/y.
EAN achieves such a high value, because EAN assumes 100% displacement of fuel (gas, propane, fuel oil), which is completely unrealistic, because the actual fuel displacement in Vermont houses with HPs was only 27.6%, based on a VT-DPS-sponsored survey of HPs in Vermont, and 35% in my well-insulated/well-sealed VT house, as above stated.
The EAN 100% claim would be true, only for highly sealed and highly insulated houses, which represent about 1.5% of all Vermont houses.
In addition, the average Vermont house would need 2 to 3 HPs, at a turnkey cost of at least $20,000, to achieve 100% displacement. See URL
https://www.eanvt.org/wp-content/uploads/2020/03/EAN-report-2020-fi...
Table 1/CO2 Reduction
|
With HP
|
With HP
|
Fuel displaced 35%
|
Electricity
|
Electricity
|
|
Market based
|
Location based
|
Electricity CO2, g/kWh
|
33.9
|
317
|
CO2 of 2489 kWh, Mt/y
|
0.084
|
0.789
|
CO2 of 550 gal of propane, Mt/y
|
3.168
|
3.168
|
Total CO2 with HPs, Mt/y
|
3.253
|
3.957
|
CO2 of 850 gal of propane, Mt/y
|
4.897
|
4.897
|
CO2 reduction, Mt/y
|
1.644
|
0.939
|
.
|
|
|
Fuel displaced 100%
|
|
|
CO2 reduction by EAN, Mt/y
|
4.111
|
4.111
|
PART 3
HP Operating Cost During a Heating Season
If HPs are operated at low temperatures, they have low COPs, which would result in a greater electricity cost per hour than using the displaced fuel.
See table 3 and page 5 of URL
At 27.6% Fuel Displacement: Vermont houses with HPs, operated down to about 28F, would require 2,085 kWh/y, to deliver 21,400,000 Btu, at an average COP of 3.34, to displace 27.6% of space heat, at an electricity cost of $417/y, per VT-DPS survey
At 35% Fuel Displacement: My HPs, operated down to 15F, would require about 2,489 kWh/y, to deliver 20,220,000 Btu, at an average COP of 2.64, to displace 35% of my space heat, at an electricity cost of $498/y
At 100% Fuel Displacement: My HPs, operated down to -10F, would require about 8,997 kWh/y, to deliver 57,290,000 Btu, at an average COP of 2.07, to displace 100% of my space heat, at an electricity cost of $1,799/y.
This would displace 850 gal of propane, at a cost of 850 x $2.339/gal = $1,988/y.
My energy cost savings would be 1,988 - 1,799 = $189/y, on an investment of $24,000 !!!
Comments on table 2
- Vermont HP data was from VT-DPS survey. See Appendix and table 4
- My HPs were operated down to 15F, which is less than the VT HPs, hence my average COP = 2.64
- Most VT HPs are operated down to about 28F; the traditional space heating system is operated below 28F. See figure 14 of URL
- I can operate down to 15F, because of better insulation and sealing than an average Vermont house.
- If my HPs were operated down to -10F, i.e., 100% fuel displacement, my average COP would be 2.07
https://publicservice.vermont.gov/sites/dps/files/documents/2017%20Evaluation%20of%20Cold%20Climate%20Heat%20Pumps%20in%20Vermont.pdf
BTW, all energy systems engineers, including at EAN, know this, because every engineering college teaches that subject to its students.
Table 2
|
Vermont HPs
|
My HPs
|
|
Before HPs
|
|
Fuel Displacement, %
|
27.6
|
35%
|
100%
|
Propane
|
|
Operation
|
Down to 28F
|
Down to 15F
|
Down to -10F
|
|
|
Purchased electricity, kWh
|
2085
|
2489
|
8997
|
850
|
Gal
|
Standby, kWh
|
76
|
91
|
329
|
0.8
|
Efficiency
|
Defrost, kWh
|
129
|
154
|
557
|
84250
|
Btu/gal, LHV
|
Electricity to HPs, kWh
|
1880
|
2244
|
8111
|
|
|
COP
|
3.34
|
2.64
|
2.07
|
|
|
Space heat, kWh
|
6279
|
5926
|
16791
|
|
|
Btu/kWh
|
3412
|
3412
|
3412
|
|
|
Space heat, kWh
|
21400000
|
20220000
|
57290000
|
57290000
|
|
Highly Sealed, Highly Insulated Housing
If I had a highly sealed, highly insulated house, with the same efficient propane heating system, my house, for starters, would use very little energy for space heating, i.e., not much additional energy cost saving and additional CO2 reduction would be possible using HPs
If I would install HPs, and would operate the propane system down to 5F (which would involve greater defrost losses), I likely would displace a greater percentage of propane, and might have greater annual energy cost savings; much would depend on: 1) the total energy consumption, which is very little, because of my higher-efficiency house, and 2) the prices of electricity and propane. See Note.
I likely would need 3 units at 18,000 Btu/h, at a lesser turnkey capital cost. Their output, very-inefficiently produced (low COP), would be about 34,000 Btu/h at -10F, the Vermont HVAC design temperature.
However, any annual energy cost savings would be overwhelmed by the annual amortizing cost, and parts and service costs. i.e., I would still be losing money, if amortizing were considered.
NOTE:
1) About 1.5 percent of Vermont houses are highly sealed and highly insulated, i.e., suitable for economic use of HPs
2) Vermont’s weatherizing program, at about $10,000/unit, does next to nothing for making energy-hog houses suitable for HPs; it is a social program for poorer people.
Table 3 shows, I could have operated my HPs down to about 10F, instead of 15F, and break even regarding hourly cost of operation.
My 35% fuel displacement likely would increase to about 40 percent.
Table 3 shows, the cost of space heating at -10F is about 1.95/0.49 = 4 times greater than at 30F, whereas the space heat demand increased 40,000/20,000 = 2 times, due to HPs having low COPs at low temperatures, per Engineering Thermodynamics 101
BTW, the electricity draw by all HPs would place a high burden on pocket books and distribution grids, during such cold periods, at about the same time all those EVs would be charging.
In table 3, the COPs at low temperatures, 35F to 10F (bold), were adjusted downward for defrost losses.
The COPs, determined by manufacturers in a laboratory, exclude defrost losses, which were about 6.2%, per VT-DPS survey. See Appendix and URL
Most RE folks who write about, or analyze HPs: 1) fail to mention those losses, and 2) do not adjust the COPs
https://publicservice.vermont.gov/sites/dps/files/documents/2017%20...
Cascading Benefits of a Highly Sealed and Highly Insulated Housing Stock
If my house were highly sealed and highly insulated, R-40 or better, R20 basement, etc.:
1) The space heat demand would be about 50% of the table values, such as 20,000 Btu/h at -10F
2) The electricity and propane cost would also be about 50% of the table values
3) The burden on the distribution grids and transmission grids would be about 50% less.
4) The need for new power plants and electric grids would be less.
All that falls under the heading, “putting the horse before the cart”, i.e., highly efficient housing stock first, then HPs
Table 3
|
Heat
|
Propane
|
HP
|
Elect
|
Diff.
|
Outdoor Temp
|
Demand
|
Cost
|
COP
|
Cost
|
|
F
|
Btu/h
|
$/h
|
|
$/h
|
$/h
|
-10
|
40000
|
1.39
|
1.20
|
1.95
|
0.57
|
0
|
35000
|
1.21
|
1.45
|
1.41
|
0.20
|
5
|
32500
|
1.13
|
1.55
|
1.23
|
0.10
|
10
|
30000
|
1.04
|
1.75
|
1.00
|
-0.04
|
15
|
27500
|
0.95
|
1.85
|
0.87
|
-0.08
|
17
|
26500
|
0.92
|
2.14
|
0.73
|
-0.19
|
20
|
25000
|
0.87
|
2.45
|
0.60
|
-0.27
|
30
|
20000
|
0.69
|
3.00
|
0.39
|
-0.30
|
35
|
17500
|
0.61
|
3.30
|
0.31
|
-0.30
|
40
|
15000
|
0.52
|
3.70
|
0.24
|
-0.28
|
47
|
11500
|
0.40
|
4.19
|
0.16
|
-0.24
|
50
|
10000
|
0.35
|
4.40
|
0.13
|
-0.21
|
60
|
5000
|
0.17
|
5.10
|
0.06
|
-0.12
|
70
|
0
|
|
|
|
|
Heat Pump Evaluation in Minnesota
The image on page 10 of URL shows:
1) Increasing COPs of an HP versus increasing outdoor temperatures (blue)
2) The defrost range from 37F down to 10F (yellow)
3) Operation of the propane back-up system from 20F to -20F (green).
Such operation would be least costly and would displace propane, that otherwise would be used.
The image shows, HPs are economical down to about 13 F, then propane, etc., becomes more economical; much depends on the prices of electricity and propane.
https://mn.gov/commerce-stat/pdfs/card-air-source-heat-pump.pdf
BTW, all of the above has been known for many years, in and out of government.
Ground Source HPs
They are widely used in many different buildings in northern Europe, such as Germany, the Netherlands, Denmark, Norway, Sweden and Finland.
Their main advantage is the COP does not decrease with temperature, because the ground temperature is constant
GSHPs can economically displace 100% of fuel.
HPs can economically displace at most 50% of fuel; the percentage depends on how well a building is sealed and insulated.
The main disadvantage of GSHPs is greater turnkey capital cost, i.e., high amortization cost. See URL
http://www.windtaskforce.org/profiles/blogs/residential-and-other-g...
NOTE: It is completely inane for RE folks to mindlessly repeat:
"Vermonters must have 25,000 HPs, by so and so year, to save the climate, even though it is required by the off-the-charts nutty GWSA act, and the grandiose Comprehensive Energy Plan.
The GWSA should be scrapped, and the CEP should be rewritten along realistic lines.
In the World-CO2 picture, Vermont is just a dot at the end of this sentence.
Heat Pump Evaluation in Vermont by VT-DPS
VT-Department of Public Service found, after a survey of 77 HPs installed in Vermont houses:
- The annual energy cost savings were, on average, $200, but the maintenance and annual amortizing costs would turn that gain into a loss of at least $200.
- On average, the HPs provided 27.6% of the annual space heat, and traditional fuels provided 72.4%. These numbers are directly from the CADMUS report.
- Owners started to turn off their HPs at about 28F, and very few owners were using their HPs at 10F and below, as shown by the decreasing kWh consumption totals on figure 14 of URL
https://publicservice.vermont.gov/sites/dps/files/documents/2017%20...
- On average, an HP consumed 2,085 kWh during the heating season, of which:
1) To outdoor unit (compressor, outdoor fan, controls) + indoor air handling unit (fan and supplemental electric heater, if used) to provide heat 1,880 kWh;
2) Standby mode 76 kWh, or 100 x 76/2085 = 3.6%;
3) Defrost mode 129 kWh, or 100 x 129/2085 = 6.2%. Defrost starts at about 37F and ends at about 10F.
- Turnkey cost for a one-head HP system is about $4,500; almost all houses had just one HP. See URLs.
On average, these houses were unsuitable for HPs, and the owners were losing money.
http://www.windtaskforce.org/profiles/blogs/cost-savings-of-air-sou...
NOTE: Coefficient of Performance, COP = heat delivered to house/electrical energy to HP. See page 10 of URL
https://mn.gov/commerce-stat/pdfs/card-air-source-heat-pump.pdf
Displaced Fuel Percentage of Vermont Heat Pumps, based on survey
As a result of a few years of complaints by various HP users, mainly about energy cost savings being much less than stated on various websites, VT-DPS was ordered by the Legislature to hire a consultant to perform a survey. CADMUS gathered the operating data of 77 HPs at 65 sites, to determine annual energy cost savings of the heat pumps.
CADMUS calculated:
- Space heat to all sites was 65 x 92 million Btu/site = 5,980 million Btu from all fuels. See URL, page 22
- Heat from HPs was 77 x 21.4 million Btu/HP = 1,648 million Btu. See URL, page 21
- Traditional systems provided 5980 – 1648 = 4,332 million Btu, or 4332/5980 = 72.4% of the total space heat.
https://publicservice.vermont.gov/sites/dps/files/documents/2017%20...
The energy cost savings were an average of about $200/HP per year, instead of the $1,200/y to $1,800/y bandied about by RE folks and GMP, VT-DPS, VPIRG, etc. After the CADMUS report, those estimates disappeared from booster websites. See URLs.
http://www.windtaskforce.org/profiles/blogs/air-source-heat-pumps-a...
http://www.windtaskforce.org/profiles/blogs/fact-checking-regarding...
http://www.windtaskforce.org/profiles/blogs/vermont-baseless-claims...
Table 4/Space heat, per CADMUS
|
|
Sites
|
Million Btu/site
|
Million Btu
|
%
|
|
Heat to sites
|
|
65
|
92.00
|
5,980
|
|
See URL, page 22
|
|
|
HPs
|
Million Btu/HP
|
|
|
|
Heat from HPs
|
1648/5980
|
77
|
21.40
|
1,648
|
27.6
|
See URL, page 21
|
Heat from traditional
|
4332/5980
|
|
|
4,332
|
72.4
|
|
.
|
|
|
|
|
|
|
|
|
|
Million Btu/site
|
|
%
|
|
Heat from HPs, on average
|
1648/65
|
|
25.35
|
|
27.6
|
|
Heat from traditional, on average
|
92.00 – 25.35 = 66.65
|
|
66.65
|
|
72.4
|
|
|
|
|
92.00
|
|
|
|
CO2 CALCULATIONS
The EPA Proscribes Two Methods for Calculating the CO2 Per Kilowatt-hour
https://www.epa.gov/sites/default/files/2016-03/documents/electrici...
Method 1 is “location-based”. It is based on physical conditions, i.e., science-based
The CO2 of each electric power source on an electric grid is calculated, based on fuel consumption.
This method is used by the Independent Systems Operator of New England, ISO-NE.
Method 2 is “market-based” It has nothing to do with physical conditions.
The CO2 of each electric power source on an electric grid is calculated, based on EPA emission factors applicable to the electricity of commercial contracts. See page 3 of epa.gov URL
This method is used by the Vermont Department of Public Service.
Per international convention, the EPA declared wind, solar, nuclear, hydro, biomass (i.e., wood chip burning), farm methane, etc., as having zero CO2 emissions, for bookkeeping purposes.
NOTE: Electricity travels, as electromagnetic waves, at slightly less than the speed of light, i.e., almost 1860 mile in 0.01 second, i.e., from northern Maine to southern Florida in 0.01 second! The electrons largely vibrate in place at 60 cycles per second.
It is nonsense for RE folks to talk of the “Vermont Energy mix”, or the “New Hampshire energy mix”, or to use a “paper PPA energy mix”. These fictitious mixes have no physical basis.
BTW, if electricity did not travel that fast, the operation of electric grids would be physically impossible.
https://vermontbiz.com/news/2021/may/20/vermont-makes-progress-carb...
https://www.windtaskforce.org/profiles/blogs/poor-economics-of-elec...
Method 1, Location-Based
NE Grid CO2 Emissions, as calculated by ISO-NE
In 2019, about 82% of electricity loaded onto the NE grid was generated in NE, and 18% was imported. See Note and table in epa URL
The ISO-NE-calculated CO2 emissions for 2019 = (30.997 million US ton, see iso-ne emissions URL x 2000lb/US ton x 454 g/lb)/ (97,853,000 MWh, NE generation, per epa URL) x 1000 kWh/MWh) = 288 g/kWh, fed-to-grid basis, or 288/0.908 = 317 g/kWh, fed-to-user-meter basis, i.e., consumption based, if total grid loss = 2.5%, NE grid + 6.7%, distribution grids = 9.2%.
The grid CO2/kWh will be slowly decreasing as more low-CO2 electricity generators, such as wind, solar, nuclear, hydro, biomass (i.e., wood chip burning), farm methane, etc., are added to the electricity mix of the NE grid.
https://www.iso-ne.com/static-assets/documents/2021/03/2019_air_emi...
https://www3.epa.gov/region1/npdes/merrimackstation/pdfs/ar/AR-1744...
NOTE: Since 2004, lower-priced electricity has been imported to serve NE demand; much of it is Canadian hydropower. The CO2 of the imports does not count toward NE grid emissions, by convention, because that CO2 is assumed to be counted in the “jurisdiction of origin”. See URL
https://www.iso-ne.com/about/key-stats/air-emissions
Method 2, Market-Based
Vermont Electrical Sector CO2 Emissions, as calculated by VT-DPS
VT-DPS, without providing any calculations, announced the CO2 emissions of the VT electrical sector were 1,000,000; 810,000; 490,000; 190,000; and 130,000 metric ton, for 2015 through 2019.
See page 36 of URL
https://dec.vermont.gov/sites/dec/files/aqc/climate-change/document...
The VT-DPS emissions were almost entirely “market-based”, i.e., based on EPA emission factors applicable to the electricity of power purchase agreements, PPAs
VT utilities are legally required to have PPAs with the owners of in-state and out-of-state electricity producers
If VT utilities did not have such PPAs, they would be drawing electricity from the NE grid without contracts, which is the legal equivalent of stealing!
Physically, VT utilities draw about 95% of their annual 6.0 billion electricity supply from the NE high voltage grid, i.e., they draw the mix of the NE grid.
The remaining 5% is fed to utility-owned distribution grids, such as rooftop solar. See Note
Because of losses, about 5.6 billion kWh/y arrives at user meters, a distribution loss of about 100 x (1- 5.6/6.0) = 6.7%
VT-DPS-calculated CO2 emissions for 2019 = 130,000 Mt/y / 5.6 billion kWh/y = 23 g CO2/kWh, fed-to-user-meter basis, i.e., consumption based, or only 100 x {1 - (1 - 23/317)} = 7.3% of the ISO-NE value.
VT Location-based CO2, in 2019, was about 5.6 billion x 317 g/kWh = 1,773,918 Mt, per ISO-NE fuel data.
VT Market-based CO2, in 2019, was about 130,000 Mt, per PPAs.
The market-based method enabled GMP to proclaim itself to be 95% CO2-free, without spending one dime, because it signed PPAs for wind, solar, nuclear, hydro, biomass (i.e., wood chip burning), farm methane, etc., which are designated as having zero CO2 emissions, per international convention.
.
APPENDIX 1
World Offshore Wind Capacity Placed on Operation in 2021
During 2021, worldwide offshore wind capacity placed in operation was 17,398 MW, of which China 13,790 MW, and the rest of the world 3,608 MW, of which UK 1,855 MW; Vietnam 643 MW; Denmark 604 MW; Netherlands 402 MW; Taiwan 109 MW
Of the 17,398 MW, just 57.1 MW was floating, about 1/3%
At end of 2021, 50,623 MW was in operation, of which just 123.4 MW was floating, about 1/4%
https://www.energy.gov/eere/wind/articles/offshore-wind-market-repo...
Floating Offshore Wind Systems in the Impoverished State of Maine
https://www.windtaskforce.org/profiles/blogs/floating-offshore-wind...
Despite the meager floating offshore MW in the world, pro-wind politicians, bureaucrats, etc., aided and abetted by the lapdog Main Media and "academia/think tanks", in the impoverished State of Maine, continue to fantasize about building 3,000 MW of 850-ft-tall floating offshore wind turbines by 2040!!
Maine government bureaucrats, etc., in a world of their own climate-fighting fantasies, want to have about 3,000 MW of floating wind turbines by 2040; a most expensive, totally unrealistic goal, that would further impoverish the already-poor State of Maine for many decades.
Those bureaucrats, etc., would help fatten the lucrative, 20-y, tax-shelters of mostly out-of-state, multi-millionaire, wind-subsidy chasers, who likely have minimal regard for:
1) Impacts on the environment and the fishing and tourist industries of Maine, and
2) Already-overstressed, over-taxed, over-regulated Maine ratepayers and taxpayers, who are trying to make ends meet in a near-zero, real-growth economy.
Those fishery-destroying, 850-ft-tall floaters, with 24/7/365 strobe lights, visible 30 miles from any shore, would cost at least $7,500/ installed kW, or at least $22.5 billion, if built in 2023 (more after 2023)
Almost the entire supply of the Maine projects would be designed and made in Europe, then transported across the Atlantic Ocean, in European specialized ships, then unloaded at a new, $500-million Maine storage/pre-assembly/staging/barge-loading area, then barged to European specialized erection ships for erection of the floating turbines. The financing will be mostly by European pension funds paying pensions to retirees.
About 300 Maine people would have jobs during the erection phase
The other erection jobs would be by specialized European people, mostly on cranes and ships
About 100 Maine people would have long-term O&M jobs, using European spare parts, during the 20-y electricity production phase.
https://www.maine.gov/governor/mills/news/governor-mills-signs-bill...
The Maine woke bureaucrats are falling over each other to prove their “greenness”, offering $millions of this and that for free, but all their primping and preening efforts has resulted in no floating offshore bids from European companies
The Maine people have much greater burdens to look forward to for the next 20 years, courtesy of the Governor Mills incompetent, woke bureaucracy that has infested the state government
The Maine people need to finally wake up, and put an end to the climate scare-mongering, which aims to subjugate and further impoverish them, by voting the entire Democrat woke cabal out and replace it with rational Republicans in 2024
The present course leads to financial disaster for the impoverished State of Maine and its people.
The purposely-kept-ignorant Maine people do not deserve such maltreatment
Electricity Cost: Assume a $750 million, 100 MW project consists of foundations, wind turbines, cabling to shore, and installation at $7,500/kW.
Production 100 MW x 8766 h/y x 0.40, CF = 350,640,000 kWh/y
Amortize bank loan for $525 million, 70% of project, at 6.5%/y for 20 years, 13.396 c/kWh.
Owner return on $225 million, 30% of project, at 10%/y for 20 years, 7.431 c/kWh
Offshore O&M, about 30 miles out to sea, 8 c/kWh.
Supply chain, special ships, and ocean transport, 3 c/kWh
All other items, 4 c/kWh
Total cost 13.396 + 7.431 + 8 + 3 + 4 = 35.827 c/kWh
Less 50% subsidies (ITC, 5-y depreciation, interest deduction on borrowed funds) 17.913 c/kWh
Owner sells to utility at 17.913 c/kWh
NOTE: The above prices compare with the average New England wholesale price of about 5 c/kWh, during the 2009 - 2022 period, 13 years, courtesy of:
Gas-fueled CCGT plants, with low-cost, low-CO2, very-low particulate/kWh
Nuclear plants, with low-cost, near-zero CO2, zero particulate/kWh
Hydro plants, with low-cost, near-zero-CO2, zero particulate/kWh
Cabling to Shore Plus $Billions for Grid Expansion on Shore: A high voltage cable would be hanging from each unit, until it reaches bottom, say about 200 to 500 feet.
The cables would need some type of flexible support system
There would be about 5 cables, each connected to sixty, 10 MW wind turbines, making landfall on the Maine shore, for connection to 5 substations (each having a 600 MW capacity, requiring several acres of equipment), then to connect to the New England HV grid, which will need $billions for expansion/reinforcement to transmit electricity to load centers, mostly in southern New England.
Floating Offshore a Major Financial Burden on Maine People: Rich Norwegian people can afford to dabble in such expensive demonstration follies (See Appendix 2), but the over-taxed, over-regulated, impoverished Maine people would buckle under such a heavy burden, while trying to make ends meet in the near-zero, real-growth Maine economy. Maine folks need lower energy bills, not higher energy bills.
APPENDIX 2
Floating Offshore Wind in Norway
Equinor, a Norwegian company, put in operation, 11 Hywind, floating offshore wind turbines, each 8 MW, for a total of 88 MW, in the North Sea. The wind turbines are supplied by Siemens, a German company
Production will be about 88 x 8766 x 0.5, claimed lifetime capacity factor = 385,704 MWh/y, which is about 35% of the electricity used by 2 nearby Norwegian oil rigs, which cost at least $1.0 billion each.
On an annual basis, the existing diesel and gas-turbine generators on the rigs, designed to provide 100% of the rigs electricity requirements, 24/7/365, will provide only 65%, i.e., the wind turbines have 100% back up.
The generators will counteract the up/down output of the wind turbines, on a less-than-minute-by-minute basis, 24/7/365
The generators will provide almost all the electricity during low-wind periods, and 100% during high-wind periods, when rotors are feathered and locked.
The capital cost of the entire project was about 8 billion Norwegian Kroner, or about $730 million, as of August 2023, when all 11 units were placed in operation, or $730 million/88 MW = $8,300/kW. See URL
That cost was much higher than the estimated 5 billion NOK in 2019, i.e., 60% higher
The project is located about 70 miles from Norway, which means minimal transport costs of the entire supply to the erection sites
The project produces electricity at about 42 c/kWh, no subsidies, at about 21 c/kWh, with 50% subsidies
In Norway, all work associated with oil rigs is very expensive.
Three shifts of workers are on the rigs for 6 weeks, work 60 h/week, and get 6 weeks off with pay, and are paid well over $150,000/y, plus benefits.
If Norwegian units were used in Maine, the production costs would be even higher in Maine, because of the additional cost of transport of almost the entire supply, including specialized ships and cranes, across the Atlantic Ocean, plus
A high voltage cable would be hanging from each unit, until it reaches bottom, say about 200 to 500 feet.
The cables would need some type of flexible support system
The cables would be combined into several cables to run horizontally to shore, for at least 25 to 30 miles, to several onshore substations, to the New England high voltage grid.
.
https://www.offshore-mag.com/regional-reports/north-sea-europe/arti...
https://en.wikipedia.org/wiki/Floating_wind_turbine
.

.
APPENDIX 3
Offshore Wind in US and UK
Most folks, seeing only part of the picture, write about wind energy issues that only partially cover the offshore wind situation, which caused major declines of the stock prices of Siemens, Oersted, etc., starting at the end of 2020; the smart money got out
All this well before the Ukraine events, which started in February 2022. See costs/kWh in below article
US/UK Governments Offshore Wind Goals
1) 30,000 MW of offshore by 2030, by the cabal of climate extremists in the US government
2) 36,000 MW of offshore by 2030, and 40,000 MW by 2040, by the disfunctional UK government
Those US/UK goals are physically unachievable, even with abundant, low-cost financing, and low inflation, and low-cost energy, materials, labor, and a robust, smooth-running supply chain, to place in service about 9500 MW of offshore during each of the next 7 years, from start 2024 to end 2030, which has never been done before in such a short time. See URL
US/UK 66,000 MW OF OFFSHORE WIND BY 2030; AN EXPENSIVE FANTASY
https://www.windtaskforce.org/profiles/blogs/biden-30-000-mw-of-off...
US Offshore Wind Electricity Production and Cost
Electricity production about 30,000 MW x 8766 h/y x 0.40, lifetime capacity factor = 105,192,000 MWh, or 105.2 TWh. The production would be about 100 x 105.2/4000 = 2.63% of the annual electricity loaded onto US grids.
Electricity Cost, c/kWh: Assume a $550 million, 100 MW project consists of foundations, wind turbines, cabling to shore, and installation, at $5,500/kW.
Production 100 MW x 8766 h/y x 0.40, CF = 350,640,000 kWh/y
Amortize bank loan for $385 million, 70% of project, at 6.5%/y for 20 y, 9.824 c/kWh.
Owner return on $165 million, 30% of project, at 10%/y for 20 y, 5.449 c/kWh
Offshore O&M, about 30 miles out to sea, 8 c/kWh.
Supply chain, special ships, ocean transport, 3 c/kWh
All other items, 4 c/kWh
Total cost 9.824 + 5.449 + 8 + 3 + 4 = 30.273 c/kWh
Less 50% subsidies (ITC, 5-y depreciation, interest deduction on borrowed funds) 15.137 c/kWh
Owner sells to utility at 15.137 c/kWh; developers in NY state, etc., want much more. See Above.
Not included: At a future 30% wind/solar penetration on the grid:
Cost of onshore grid expansion/reinforcement, about 2 c/kWh
Cost of a fleet of plants for counteracting/balancing, 24/7/365, about 2.0 c/kWh
In the UK, in 2020, it was 1.9 c/kWh at 28% wind/solar loaded onto the grid
Cost of curtailments, about 2.0 c/kWh
Cost of decommissioning, i.e., disassembly at sea, reprocessing and storing at hazardous waste sites
.
APPENDIX 4
Levelized Cost of Energy Deceptions, by US-EIA, et al.
Most people have no idea wind and solar systems need grid expansion/reinforcement and expensive support systems to even exist on the grid.
With increased annual W/S electricity percent on the grid, increased grid investments are needed, plus greater counteracting plant capacity, MW, especially when it is windy and sunny around noon-time.
Increased counteracting of the variable W/S output, places an increased burden on the grid’s other generators, causing them to operate in an inefficient manner (more Btu/kWh, more CO2/kWh), which adds more cost/kWh to the offshore wind electricity cost of about 16 c/kWh, after 50% subsidies
The various cost/kWh adders start with annual W/S electricity at about 8% on the grid.
The adders become exponentially greater, with increased annual W/S electricity percent on the grid
The US-EIA, Lazard, Bloomberg, etc., and their phony LCOE "analyses", are deliberately understating the cost of wind, solar and battery systems
Their LCOE “analyses” of W/S/B systems purposely exclude major LCOE items.
Their deceptions reinforced the popular delusion, W/S are competitive with fossil fuels, which is far from reality.
The excluded LCOE items are shifted to taxpayers, ratepayers, and added to government debts.
W/S would not exist without at least 50% subsidies
W/S output could not be physically fed into the grid, without items 2, 3, 4, 5, and 6. See list.
1) Subsidies equivalent to about 50% of project lifetime owning and operations cost,
2) Grid extension/reinforcement to connect remote W/S systems to load centers
3) A fleet of quick-reacting power plants to counteract the variable W/S output, on a less-than-minute-by-minute basis, 24/7/365
4) A fleet of power plants to provide electricity during low-W/S periods, and 100% during high-W/S periods, when rotors are feathered and locked,
5) Output curtailments to prevent overloading the grid, i.e., paying owners for not producing what they could have produced
6) Hazardous waste disposal of wind turbines, solar panels and batteries. See image.
.

.
APPENDIX 5
BATTERY SYSTEM CAPITAL COSTS, OPERATING COSTS, ENERGY LOSSES, AND AGING
https://www.windtaskforce.org/profiles/blogs/battery-system-capital...
EXCERPT:
Annual Cost of Megapack Battery Systems; 2023 pricing
Assume a system rated 45.3 MW/181.9 MWh, and an all-in turnkey cost of $104.5 million, per Example 2
Amortize bank loan for 50% of $104.5 million at 6.5%/y for 15 years, $5.484 million/y
Pay Owner return of 50% of $104.5 million at 10%/y for 15 years, $6.765 million/y (10% due to high inflation)
Lifetime (Bank + Owner) payments 15 x (5.484 + 6.765) = $183.7 million
Assume battery daily usage for 15 years at 10%, and loss factor = 1/(0.9 *0.9)
Battery lifetime output = 15 y x 365 d/y x 181.9 MWh x 0.1, usage x 1000 kWh/MWh = 99,590,250 kWh to HV grid; 122,950,926 kWh from HV grid; 233,606,676 kWh loss
(Bank + Owner) payments, $183.7 million / 99,590,250 kWh = 184.5 c/kWh
Less 50% subsidies (ITC, depreciation in 5 years, deduction of interest on borrowed funds) is 92.3c/kWh
At 10% throughput, (Bank + Owner) cost, 92.3 c/kWh
At 40% throughput, (Bank + Owner) cost, 23.1 c/kWh
Excluded costs/kWh: 1) O&M; 2) system aging, 1.5%/y, 3) 20% HV grid-to-HV grid loss, 4) grid extension/reinforcement to connect battery systems, 5) downtime of parts of the system, 6) decommissioning in year 15, i.e., disassembly, reprocessing and storing at hazardous waste sites. Excluded costs would add at least 15 c/kWh
NOTE: The 40% throughput is close to Tesla’s recommendation of 60% maximum throughput, i.e., not charging above 80% full and not discharging below 20% full, to achieve a 15-y life, with normal aging
Tesla’s recommendation was not heeded by the Owners of the Hornsdale Power Reserve in Australia. They excessively charged/discharged the system. After a few years, they added Megapacks to offset rapid aging of the original system, and added more Megapacks to increase the rating of the expanded system.
http://www.windtaskforce.org/profiles/blogs/the-hornsdale-power-reserve-largest-battery-system-in-australia
COMMENTS ON CALCULATION:
Regarding any project, the bank and the owner have to be paid.
Therefore, I amortized the bank loan and the owner’s investment
If you divide total payments over 15 years by throughput during 15 years, you get the cost per kWh, as shown.
According to EIA annual reports, almost all battery systems have throughputs less than 10%. I chose 10% for calculations.
A few battery systems have higher throughputs, if used to absorb midday solar and discharge it during peak hour periods of late-afternoon/early-evening. They may reach up to 40% throughput. I chose 40% for calculations.
Remember, you have to draw about 50 MWh from the HV grid to deliver about 40 MWh to the HV grid, because of A-to-Z system losses. That gets worse with aging.
A lot of people do not like these c/kWh numbers, because they have been repeatedly told by self-serving folks, low-cost battery Nirvana is just around the corner.
You need to be a member of Citizens' Task Force on Wind Power - Maine to add comments!
Join Citizens' Task Force on Wind Power - Maine