PROTECTING BOILERS AGAINST FLUE GAS CONDENSATION

PROTECTING BOILERS AGAINST FLUE GAS CONDENSATION

https://www.achrnews.com/articles/135513-protecting-boilers-against... 

 

NON-CONDENSING BOILERS USING PROPANE OR NATURAL GAS

If the thermostats in the buildings connected to a boiler are set so the buildings can use the entire hot water output of a boiler, at say 110F, that’s as hot as the water temperature leaving the boiler will get. It doesn’t need to increase, and won’t, even if the boiler’s high limit controller was set to 140F, 180F, or 220F. The conditions for thermal equilibrium are achieved at a supply water temperature of 110F, thus the first law of thermodynamics is satisfied. End of story.

The hot water returning temperature, say 90F, entering the noncondensing boiler would be well below the dewpoint of the flue gases, i.e., the noncondensing boiler has been forced to operate as a condensing boiler.

The condensate of natural gas and propane boilers primarily would be water. However, several other chemical compounds would make the condensate acidic with a pH of about 4.0

The condensate would corrode ferrous metals and copper. It would chemically eat away at the boiler’s heat exchanger as well as the inside of the vent connector. Figure 1 of URL shows the results after only one year of operation.

https://www.achrnews.com/articles/135513-protecting-boilers-against...

The presence or absence of sustained flue gas condensation is determined by the temperature of the water entering the boiler and the air/fuel ratio at which combustion occurs. Of these, only the boiler inlet water temperature is easily controllable.

OLD DAYS

Several decades ago, sustained flue gas condensation was seldom a problem. Boilers would send out hot water at 180F - 200F

During a cold-start, a small amount of flue gas condensation would form within the boiler. However, the operating conditions would quickly increase the water temperature entering the boiler above the dewpoint and any condensate would quickly evaporate. This situation occurs in every boiler during a cold start and is generally not a problem.

MODERN DAYS

When radiant-panel heating made its comeback in North America in the 1980s, conventional boilers were paired with low-temperature distribution systems, i.e., sustained flue gas condensation on the outside of the boiler tubes, which rapidly caused erosion and leaks. Fortunately, there are ways to avoid such condensation.

Sustained flue gas condensation is avoided by monitoring the water temperature entering the boiler and react to that temperature by limiting the rate at which heat is extracted from the boiler to the distribution system. This requires the use of a mixing assembly between the boiler and distribution system.

The mixing assembly determines if the distribution system is extracting heat faster than heat production by the boiler. If heat extraction exceeds heat production, thermodynamics demands the hot water temperature in the system to decrease until the rate of heat extraction equals heat production.

If this requires the boiler to operate well below the dewpoint of its flue gases — so be it. Thermodynamics doesn’t care if the boiler is condensing; it only cares about balancing heat extraction with heat production.

The mixing assembly protects the boiler by reducing heat extraction from the boiler to the distribution system, whenever the boiler temperature decreases below a specified minimum operating temperature.

This protection partially unloads the boiler from the distribution system, allowing the boiler temperature to quickly increase above condensing conditions. This action lifts the combustion side of the boiler’s heat exchanger (the outside of the tubes) above the dewpoint of the flue gases.

THREE MODES OF OPERATION

Figures 2, 3, and 4 of the URL illustrate situations in which a conventional boiler is, and is not, protected from flue gas condensation. These systems all use a three-way mixing valve to control the temperature of the water to the distribution system. In each case, the controller operating the mixing valve is set to supply hot water at up to 125F to the heating zones.

The manifold station in each system serves six heating zones with radiant panels, each being 300 feet of ½-inch PEX tubing embedded at 12-inch spacing in a 4-inch-thick concrete slab, which would be insulated only at the bottom surface to ensure heat would travel upwards.

The systems each have a conventional boiler with a rated output of 50,000 Btu/h, sufficient for an average 2000 sq ft house in New England on a cold winter day.

System of Figure 2: The system in Figure 2 does not measure boiler inlet temperature. The water temperatures shown are those required based on a thermodynamic heat balance with the boiler in continuous operation, i.e., heat extraction equals heat production. In this case, the distribution system requires water at 5.5 gpm at 111.4F to supply 50,000 Btu/h.

Because the mixing valve controller is trying to achieve a supply water temperature of 125F and only has water at 111.4F available from the boiler, the hot port of the mixing valve is fully open and the cool port completely shut. Hence, the mixing valve is simply passing through the entering water stream directly to the manifold station. No mixing occurs.

All water exiting the return manifold flows directly back to the boiler at 93F. This low temperature would cause sustained flue gas condensation within the boiler.

System of Figure 3: The system in Figure 3 adds a bypass circulator between the boiler and mixing valve. The three-way mixing valve is correctly coupled to the boiler bypass piping using a pair of closely spaced tees. These tees provide hydraulic separation between the bypass circulator and the distribution circulator. The intent of the bypass circulator is to mix higher temperature water leaving the boiler into the cooler water returning from the distribution system, thus boosting boiler inlet temperature.

The water temperatures shown are those required based on a thermodynamic heat balance with the boiler in continuous operation, i.e., heat extraction equals heat production. Although the bypass circulator increases the flow rate through the boiler, it cannot adjust the rate of heat transfer to the distribution system relative to the rate of heat production in the boiler.

The manifold station still requires 5.5 gpm at 111.4F and returns the same flow at 93F to supply the 50,000 Btu/h added to the water by the boiler. The hot port of the mixing valve is again fully open and passing all entering hot water directly to the manifold station. No mixing occurs.

The bypass circulator and boiler loop create a second mixing point within the lower of the two closely spaced tees. The mixing at this location slightly boosts boiler inlet temperature, but not enough to prevent sustained flue gas condensation within the boiler.

Installing a larger bypass circulator would increase the flow rate through the boiler and further increase the boiler inlet temperature. The temperature difference across the boiler would decrease in response to the higher flow rate. However, no matter how high the flow rate, the boiler inlet temperature could never reach its outlet temperature. Sustained flue gas condensation would occur within the boiler.

System of Figure 4: The missing element is a mixing system that senses and reacts to the boiler inlet temperature. It would enable the boiler to be operated at higher inlet and outlet water temperatures, thereby avoiding any flue gas condensation.

The system in Figure 4 uses a mixing valve controller that measures boiler inlet temperature. The operating logic within this controller gives priority to maintaining the boiler inlet temperature above a user-selected minimum value, which, in this example is set at 130F.

The water entering the boiler would be 20 gpm at 130F, and its outlet temperature would be 135.4F for an increase of only be 5.4F.

A part of this higher temperature water enters the hot port of the mixing valve (2.39 gpm at 135.4F). Of the building return flow (5.5 gpm at 93F) about 3.11 gpm at 93F is added to yield 5.5 gpm at 111.4F to the heating zones.

The system stabilizes at the conditions shown in figure 4; the heating zones are supplied with water at 111.4F and release heat at 50,000 Btu/h, and the boiler inlet temperature remains at the mixing valve controller’s set minimum value of 130F.

A thermodynamic balance between the boiler and distribution system is achieved, and the boiler inlet temperature is high enough to avoid flue gas condensation.

The key to the successful strategy shown in Figure 4 is a mixing assembly that senses and reacts to boiler inlet temperature. This detail was lacking in the systems shown in Figures 2 and 3.

Alternative Mixing Methods:The systems shown in Figure 4 uses a motorized three-way valve as the main component of the mixing assembly. Alternatives to this mixing method include:

- Motorized four-way mixing valves and injection mixing using a variable-speed pump

- Motorized two-way injection valve.

When properly applied, these mixing assemblies also can protect a conventional boiler against flue gas condensation.

Biomass Fuel Boilers: Boilers burning cordwood, wood chips, and wood pellets are used to supply low-temperature distribution systems. These biomass fuel boilers require protection against sustained flue gas condensation and can be equipped with the same type of hardware to provide that protection.

However, the flue gases of such biomass boilers contain vastly more chemical pollutants and particulates than propane and natural gas boilers. Those chemical pollutants and particulates would deposit on the outside of the boiler tubes, thereby reducing heat transfer from the flue gases to the hot water. Periodic cleaning would be required during a heating season, which would increase the operating and maintenance costs of biomass fuel boilers.

APPENDIX 1

Test Results of Residential Water Heating Boilers and Air Heating Furnaces

 

Here are some results of PM and efficiency testing of various heating units, using various fuels, performed by engineers of the Brookhaven National Laboratory and the EPA.

 

PM Tests: The PM emissions were based on MJ of fuel input. The results of the tests were:

 

1) Gas-fired units have the lowest PM emissions averaging 0.011 to 0.016 mg/MJ

 

2) Regarding fuel oil units:

 

- Ultra low sulfur fuel-oil-units have PM emissions of 0.025 to 0.060 mg/MJ,

- Low sulfur fuel-oil units have PM emissions of 0.49 to 0.510 mg/MJ

- Typical sulfur No-2 fuel-oil units have PM emissions of 1.320 to 2.100 mg/MJ

- Pellet units have PM emissions of 25 mg/MJ; even the cleanest ones in 2020 would be off the charts dirtier than all fuel oil and gas units.

 

3) Wood pellet stoves have emissions averaging 25 mg/MJ, about 1852 times worse than gas.

 

NOTE: Cordwood stoves were not tested.

 

Older cord wood stoves have about 5 times the PM and PAH of EPA-certified pellet stoves.

New cord wood stoves, EPA-certified, have about 2 times the PM and PAH of EPA-certified pellet stoves.

 

Table 3/ Household Appliance

Hot water boiler

Warm air furnace

Times worse than gas

Particle size

 PM2.5 and smaller

 PM2.5 and smaller

 

Units

mg/MJ

mg/MJ

 

Natural gas

0.016

0.011

1.0

ULS fuel oil, 15 ppm

0.025

0.060

14.6

LS fuel oil, 500 ppm

0.490

0.510

50

No. 2 fuel oil, 2000 ppm

1.320

2.100

588

Wood pellet; 3-stove average

25.000

25.000

1852

Views: 737

Comment

You need to be a member of Citizens' Task Force on Wind Power - Maine to add comments!

Join Citizens' Task Force on Wind Power - Maine

 

Maine as Third World Country:

CMP Transmission Rate Skyrockets 19.6% Due to Wind Power

 

Click here to read how the Maine ratepayer has been sold down the river by the Angus King cabal.

Maine Center For Public Interest Reporting – Three Part Series: A CRITICAL LOOK AT MAINE’S WIND ACT

******** IF LINKS BELOW DON'T WORK, GOOGLE THEM*********

(excerpts) From Part 1 – On Maine’s Wind Law “Once the committee passed the wind energy bill on to the full House and Senate, lawmakers there didn’t even debate it. They passed it unanimously and with no discussion. House Majority Leader Hannah Pingree, a Democrat from North Haven, says legislators probably didn’t know how many turbines would be constructed in Maine if the law’s goals were met." . – Maine Center for Public Interest Reporting, August 2010 https://www.pinetreewatchdog.org/wind-power-bandwagon-hits-bumps-in-the-road-3/From Part 2 – On Wind and Oil Yet using wind energy doesn’t lower dependence on imported foreign oil. That’s because the majority of imported oil in Maine is used for heating and transportation. And switching our dependence from foreign oil to Maine-produced electricity isn’t likely to happen very soon, says Bartlett. “Right now, people can’t switch to electric cars and heating – if they did, we’d be in trouble.” So was one of the fundamental premises of the task force false, or at least misleading?" https://www.pinetreewatchdog.org/wind-swept-task-force-set-the-rules/From Part 3 – On Wind-Required New Transmission Lines Finally, the building of enormous, high-voltage transmission lines that the regional electricity system operator says are required to move substantial amounts of wind power to markets south of Maine was never even discussed by the task force – an omission that Mills said will come to haunt the state.“If you try to put 2,500 or 3,000 megawatts in northern or eastern Maine – oh, my god, try to build the transmission!” said Mills. “It’s not just the towers, it’s the lines – that’s when I begin to think that the goal is a little farfetched.” https://www.pinetreewatchdog.org/flaws-in-bill-like-skating-with-dull-skates/

Not yet a member?

Sign up today and lend your voice and presence to the steadily rising tide that will soon sweep the scourge of useless and wretched turbines from our beloved Maine countryside. For many of us, our little pieces of paradise have been hard won. Did the carpetbaggers think they could simply steal them from us?

We have the facts on our side. We have the truth on our side. All we need now is YOU.

“First they ignore you, then they laugh at you, then they fight you, then you win.”

 -- Mahatma Gandhi

"It's not whether you get knocked down: it's whether you get up."
Vince Lombardi 

Task Force membership is free. Please sign up today!

Hannah Pingree on the Maine expedited wind law

Hannah Pingree - Director of Maine's Office of Innovation and the Future

"Once the committee passed the wind energy bill on to the full House and Senate, lawmakers there didn’t even debate it. They passed it unanimously and with no discussion. House Majority Leader Hannah Pingree, a Democrat from North Haven, says legislators probably didn’t know how many turbines would be constructed in Maine."

https://pinetreewatch.org/wind-power-bandwagon-hits-bumps-in-the-road-3/

© 2024   Created by Webmaster.   Powered by

Badges  |  Report an Issue  |  Terms of Service